DC Wire Size Calculator — 12V, 24V & 48V

Copper AWG or mm² sizing from voltage drop

Required Parameters

A

Use the maximum expected operating current, including relevant startup conditions.

Source to load only; the return conductor is included in the calculation.

%

A design target, not a universal legal limit.

°C

Operating conductor temperature, not ambient air. Model range: −20 to 90 °C.

Waiting for input data...

Quick Answer

Choose 12, 24 or 48 V and find the smallest listed copper size meeting your drop target. This is not a thermal ampacity recommendation.

Documentation

Size copper wire for a 12 V, 24 V or 48 V circuit

Choose a voltage preset, load current, one-way length, conductor temperature and allowable percentage drop. The calculator rounds the required metal area up to a listed mm² or AWG size. Custom supply voltage is supported up to 60 V.

The result is a voltage-drop minimum only. Thermal ampacity is NOT checked. An extremely short cable can pass the drop check while being unsafe for its current. Check the actual cable manufacturer's rating, connectors, installation conditions and fuse coordination separately.

Formula and assumptions

For equal copper outgoing and return conductors:

A = 2 × ρ(T) × L × I / ΔV

The model uses copper resistivity 0.01724 Ω·mm²/m at 20 °C and temperature coefficient 0.00393/°C. Conductor temperature is an input, not a prediction of cable heating. The factor of two includes the return wire; do not enter round-trip length.

It excludes chassis returns, copper-clad aluminum and connection resistance. A constant-power inverter may draw more current as terminal voltage falls; use an appropriate worst-case operating current instead of blindly dividing its label power by nominal voltage.

Example: 12 V, 10 A, 5 m, 3% drop

At a conductor temperature of 75 °C:

  • Allowed drop: 12 × 3% = 0.36 V.
  • Required area is approximately 5.82 mm².
  • The next listed metric size is 6 mm².
  • Estimated drop is 0.349 V / 2.91%, with approximately 3.49 W round-trip conductor loss.

This is not confirmation that every product labelled 6 mm² is suitable for the application.

At 24 V with the same 10 A and length, the allowed drop doubles, so the calculated minimum area halves. At the same load power instead of the same current, the relationship is different: current also falls.

Battery, LED and solar applications

Use this tool for cable-drop estimates in battery-to-load wiring and LED supplies, then verify thermal and protection requirements independently. It is not a complete PV string, automotive or marine wiring design tool. Motors and converters may require separate startup/transient checks.

Related tools

Knowledge Base

Does the selected wire size guarantee safety?

No. Selection checks voltage drop only. Verify the specific cable ampacity, ambient conditions, bundling, connectors and fuse coordination independently.

Do I enter both outgoing and return lengths?

Enter one-way length only. The model assumes equal copper outgoing and return conductors and includes both.

Can I use a different DC voltage?

Yes. Select Custom voltage for a positive voltage up to 60 V. This is not a full PV, marine or automotive compliance design.